Elgar - GUPS (Global UPS) Series 1920W Ruggedized Uninterruptible Power Supply
- Ruggedized
- Wide (Global) Input
- On-Line Battery Back-Up
- Transient (Spike) Suppression
- Surge Suppression
- Input Distortion Elimination
Elgar GUPS are ruggedized on-line "UPS's" that accept a broad range of worldwide utility and military AC input power. Without operator intervention, they automatically select the appropriate input power ranges to accommodate global operation.
The GUPS Series has been specifically designed to withstand the rigors of mobile applications. They meet the vibration and shock requirements as specified in MIL-STD-810E, Methods 514.4 and 516.4. Their rackmounted aluminum chassis with stainless steel hardware withstands harsh environments and provides a strong, light weight enclosure.
Applications
GUPS are especially useful for demanding field computer applications powered by engine generators where a need for ruggedization, as well as voltage and frequency variations, have traditionally been a problem for regular UPS operation. The ability to accept a broad range of AC input voltages and frequencies, as well as ruggedized construction, make the GUPS an ideal choice for the following military and commercial applications:
- Remote computer based systems
- Engine generator output conditioning
- Communications
- Remote SATCOM
- Airborne telemetry backup
- Geological exploration
- Oil field instrumentation/logging
- Data acquisition
- Military C4I
Universal Input
The GUPS 2400A AC input model provides 2400 VA/1920W of 115 VAC, 60 Hz power. It automatically selects between two input ranges of 85 to 140 VAC and 170 to 280 VAC, while accepting any frequency from 45 to 450 Hz, and provides 115 VAC, 60 Hz output power. The GUPS 2400A-104 variant providing a three phase input from 159-232 VAC line to line at frequencies from 370-430 Hz is also available.
The GUPS 2400U universal output model provides 115 VAC, 60 Hz standard U.S. power or 230 VAC, 50 Hz international power (user selectable). Without operator intervention, it automatically selects between two input ranges of 85 to140 VAC and 170 to 280 VAC, while accepting any frequency from 45 to 450 Hz.
The Elgar GUPS is tolerant of variable power associated with "soft" sources such as engine/motor generators. Stable output power is provided, without oscillating between generator and battery input, regardless of how the input power varies within the allowed ranges. This prevents battery discharge and ensures that battery power is available in the event of generator failure. Soft-start of the UPS input rectifier limits the inrush current during start-up, precluding fluctuations in the AC source voltage that could affect other loads.
Precise and Stable Output
The output is precisely regulated, providing a low distortion sine waveform. Protection of the critical load is maximized because it is continually supplied by the online inverter; the output is never dependent on the condition of the AC input, and there are no switching transients.
Low output impedance allows driving non-linear loads that draw currents with high crest factors, such as computer power supplies. The 200% overload rating of the inverter, with a greater than 3:1 crest factor, provides an enhanced capability to supply the start-up inrush current of such loads. High frequency power conversion technology is utilized for fast dynamic response to changing load conditions. Continuous overload and short circuit protection ensure reliable operation.
A shielded transformer is used to galvanically isolate the output from the AC input, DC input, and battery. The output is further protected with suppression networks that absorb high energy transients and surges that occur on the AC input. EMI filtering and the shielded isolation transformer provide transverse-mode and common-mode attenuation of electrical noise.
UPS integrity is determined through a self test that is performed automatically during start-up. Proper operation is ensured prior to energizing the critical load. After start-up, this function can also be manually selected by the user from the front panel.
Communications Interface
An RS 232 communications interface provides information to the host system about operating status and UPS parameters such as voltages and currents. Isolated relay contacts are available for remote annunciation of loss of AC input power and impending shutdown during operation from the battery.
Batteries
The GUPS 2400A and GUPS 2400U include a drawer-mounted internal battery module that is removable from the front panel without the use of tools; this allows servicing of the battery without removing the UPS from its rack.
Battery life is maximized with automatic microprocessor controlled equalization and temperature compensation during charging.
For the GUPS 2400A and GUPS 2400U, an optional external rackmounted battery pack increases the backup time to 18 minutes at full rated load; multiple packs further extend the backup.
Output |
|
---|---|
Output Voltage GUPS 2400A |
115 VAC ±2% over full range of line and load variations |
Output Voltage GUPS 2400U |
115 VAC or 230 VAC ±2% over full range of line and load |
Output Frequency GUPS 2400A |
60 Hz ±0.1% |
Output Frequency GUPS 2400U |
50 Hz or 60 Hz ±0.1% |
Efficiency |
70% from AC input |
Output Current |
21 ARMS, 63A peak |
Output Distortion |
2% maximum THD with linear loads |
Output Power |
2400 VA into ±0.8 PF load |
Output Overload |
150% for 30s; 150% to 200% for 3s |
AC to DC Crossover |
If AC input falls below or rises above the currently selected input range limits, the unit switches to battery. The GUPS 2400A-104 variant providing a three phase input from 159-232 VAC line to line at frequencies from 370-430 Hz is also available. Contact Elgar for details on this model. |
Power Loss During Crossover |
None |
Input |
|
---|---|
Input Voltage, AC |
85 to 140 VAC or 170 to 280 VAC Single Phase |
Input Current, AC |
33A at 120 VAC, 17A at 240 VAC |
Input Frequency, AC |
45 to 450 Hz |
Internal Battery Module |
192 VDC, 2.5 AH. Optional external battery packs available |
Battery Hold-Up Time |
5 minutes for internal module with 2400 VA load, 0.8 PF @ 25°C. Adding one external battery pack increases time to a minimum of 18 minutes at full rated load. Reduced loads increase backup time. |
Environmental |
|
---|---|
Altitude |
Operating 0 to 10,000 ft; non-operating 0 to 40,000 ft |
Temperature |
Operating 0° to 40°C; non-operating -40° to 65°C |
Humidity |
5 to 95% non-condensing |
General |
|
---|---|
Weight GUPS 2400A |
78 lbs, maximum without battery module. Removable internal battery module is 48 lbs (126 lbs max combined weight). GUPS 2400A-104 variant (123 lbs max combined weight). |
Weight GUPS 2400U |
83 lbs, maximum without battery module. Removable internal battery module is 48 lbs (131 lbs max combined weight). |
Dimensions |
7"H x 19"W x 25.1"L (GUPS 2400A-104) |
Internal Battery Module |
|
---|---|
Battery Descriptions (GUPS 2400A and GUPS 2400U) |
192 VDC, 2.5 AH sealed lead acid |
Configuration |
96 cells at 2.0 V, 2.5 AH in a single pullout, removable module |
Recharge Time |
4 hours, 90% full charge with integral battery charger |
Typical Minimum Hold-Up Time 2400 VA at 25°C |
5 minutes |
Microprocessor Controlled Equalization |
Batteries maintained on a temperature compensated, constant voltage float charge with automatic equalization as required |
Temperature |
Operating 0° to 40°C; non-operating -40° to 65°C |
Weight of Removable Module |
48 lbs |
Alarms and Signals |
|
---|---|
Alarms |
The audible alarm sounds for an overtemperature, loss of AC input or improper battery voltage. |
Signals |
(1) Isolated relay contacts signal loss of AC input and impending inverter shutdown due to low battery capacity and (2) RS 232 data communications for computer interface provides information on GUPS status, alarms and parameter values. |
Indicators |
|
---|---|
AC Input |
A three color LED indicates the condition of the AC input voltage. The LED is green when the AC input voltage is within the normal operating limits, amber when the voltage is close to the limits of the operating range and red when the operating voltage range is exceeded. |
Battery |
A three color LED indicates the condition of the battery. The LED is green under normal operating conditions, amber when the battery is discharging or has low capacity and red when impending inverter shutdown is approached. |
Load |
A three color LED indicates the amount of output load. The LED is green when the load is less than 80% of maximum output, amber when the load is within 80% to 105% and red when the load exceeds 105%, indicating that the inverter will shut down if the load is maintained. |
Temperature |
A two color LED indicates the overtemperature condition of the GUPS. The LED is green under normal operating conditions and red when an over- temperature occurs. |
Test |
A two color LED indicates the results of the internal self-test. A blinking light indicates the test is in progress. When the test is complete, the LED turns green if the GUPS passes the test and red if it fails. |
Controls |
|
---|---|
Output On |
Switches on or off the GUPS output |
Test |
Initiates the internal self-test |
Alarm Silence |
Silences the audible alarm |
Remote Shutdown (GUPS 2400U only) |
Switches off the UPS output and disconnects the UPS from the AC input source. Requires external SPST contact closure |
Frequency Switch |
|
---|---|
Output Frequency (GUPS 2400U only) |
Selects 50 or 60 Hz output |
Configuration Terminal Block |
|
---|---|
Output Voltage (GUPS 2400U only) |
Selects 115 VAC or 230 output |